Power Systems practice questions

10 free Power Systems questions for the FE Electrical and Computer Exam (FE) exam, each with the correct answer and an explanation for every option.

What this domain covers

Generating, transmitting and using electric power: single- and three-phase systems, transformers, machines and power factor.

Exam weight
8%
On a real exam
≈ 9 questions
In our bank
48 questions

Topics that come up most

  • Three-phase wye and delta relationships
  • Transformer ratios and equivalent circuits
  • Per-unit calculations
  • Induction and synchronous machines
  • Power factor correction and voltage regulation

How to study it

Practise the wye and delta line and phase conversions until they are automatic, keeping the \(\sqrt{3}\) factor in the right place; many power questions rely on it.

Sample Power Systems questions

Try each one before opening the answer. Original questions written to the official exam objectives.

  1. Question 1

    A distribution feeder carries 100 A, and its total conductor resistance is 0.2 Ω. What is the real power lost in the feeder resistance?

    • A500 W
    • B20 W
    • C50 kW
    • D2 kW
    Show answer and explanation

    Answer: D) 2 kW

    Resistive (copper) loss is P = I²R. Here 100² × 0.2 = 2,000 W, or 2 kW.

    • AIncorrect. This comes from dividing current by resistance (100 / 0.2), which doesn't correspond to any power formula.
    • BIncorrect. This is I·R = 100 × 0.2 = 20, which is the voltage drop in volts, not power. The current must be squared.
    • CIncorrect. This comes from I²/R = 10,000 / 0.2 = 50,000 W. Resistance should multiply, not divide.
    • DCorrect. P = I²R = (100 A)² × 0.2 Ω = 10,000 × 0.2 = 2,000 W = 2 kW.
  2. Question 2

    An open-delta connection using two transformers can supply about what share of the capacity of a full delta bank of three?

    • A57.7%
    • B66.7%, two-thirds of the bank
    • C100%
    • D33.3%
    Show answer and explanation

    Answer: A) 57.7%

    • ACorrect. It's \(1/\sqrt{3}\) of the three-transformer rating.
    • BIncorrect. The usable share is lower.
    • CIncorrect. It can't match a full bank.
    • DIncorrect. That's one transformer's share.
  3. Question 3

    To reverse the direction of a three-phase induction motor, an electrician can:

    • ALower the supply frequency
    • BSwap all three leads in a circle
    • CReverse the polarity of a DC field
    • DSwap any two of the three supply leads
    Show answer and explanation

    Answer: D) Swap any two of the three supply leads

    • AIncorrect. That changes speed, not direction.
    • BIncorrect. That keeps the same sequence.
    • CIncorrect. Induction motors have no DC field.
    • DCorrect. That reverses the phase sequence.
  4. Question 4

    An inductive load draws 12 kW of real power and 9 kvar of reactive power. What is its power factor?

    • A0.60 lagging
    • B0.75 lagging
    • C0.80 lagging
    • D0.80 leading
    Show answer and explanation

    Answer: C) 0.80 lagging

    Apparent power is S = √(P² + Q²) = 15 kVA, so PF = P/S = 0.80. It is lagging because the load is inductive.

    • AIncorrect. 9/15 = 0.60 is Q/S (the sine of the power-factor angle), not P/S.
    • BIncorrect. 9/12 = 0.75 is Q/P, which is tan θ, not cos θ.
    • CCorrect. S = √(12² + 9²) = 15 kVA, so PF = P/S = 12/15 = 0.80. It is lagging because the load is inductive and absorbs reactive power.
    • DIncorrect. The size is right, but an inductive load absorbs reactive power, so current lags voltage and the power factor is lagging.
  5. Question 5

    A 4-pole, 60-Hz induction motor runs at 1,750 rpm. Its slip is about:

    • A2.8%
    • B50%
    • C97.2%
    • D5.0%
    Show answer and explanation

    Answer: A) 2.8%

    • ACorrect. (1,800 − 1,750)/1,800.
    • BIncorrect. Divide by synchronous speed.
    • CIncorrect. That's speed as a fraction of synchronous.
    • DIncorrect. Recheck the calculation.
  6. Question 6

    A 6-pole synchronous machine operates on a 60-Hz system. Its synchronous speed is:

    • A600 rpm
    • B3,600 rpm, the 2-pole speed
    • C1,800 rpm, the 4-pole speed
    • D1,200 rpm
    Show answer and explanation

    Answer: D) 1,200 rpm

    • AIncorrect. That's for 12 poles.
    • BIncorrect. That's for 2 poles.
    • CIncorrect. That's for 4 poles.
    • DCorrect. \(N_s = 120f/P\).
  7. Question 7

    A power factor of 0.8 corresponds to a phase angle of about:

    • A0.8°
    • B53.1°
    • C80°
    • D36.9°
    Show answer and explanation

    Answer: D) 36.9°

    • AIncorrect. That isn't the conversion.
    • BIncorrect. That's \(\cos^{-1}(0.6)\).
    • CIncorrect. That isn't the conversion.
    • DCorrect. \(\cos^{-1}(0.8)\).
  8. Question 8

    Surge arresters are installed mainly to protect equipment from:

    • ALow power factor
    • BSustained overloads
    • COvervoltages such as lightning or switching surges
    • DPhase imbalance
    Show answer and explanation

    Answer: C) Overvoltages such as lightning or switching surges

    • AIncorrect. That's corrected with capacitors.
    • BIncorrect. That's overcurrent protection.
    • CCorrect. They divert surge current to ground.
    • DIncorrect. That uses other protection.
  9. Question 9

    In a radial distribution system, what is the main goal of protective relay and overcurrent device coordination when a fault occurs?

    • ARelays in the faulted zone and the adjacent zones all operate together to clear the fault as fast as possible
    • BThe device closest to the fault operates first, and upstream devices act as time-delayed backup
    • CThe upstream source-side device operates first, and downstream devices act as backup
    • DEvery relay uses the same time-current settings so that trip times match across the system
    Show answer and explanation

    Answer: B) The device closest to the fault operates first, and upstream devices act as time-delayed backup

    Coordination (selectivity) grades device settings so the device nearest the fault clears it first and upstream devices serve only as backup. This keeps the outage as small as possible.

    • AIncorrect. If adjacent zones trip together, healthy parts of the system lose power for no reason. Coordination is meant to prevent exactly that.
    • BCorrect. Selective coordination isolates only the faulted section. Upstream devices are set with enough time margin to trip only if the nearest device fails.
    • CIncorrect. This reverses the intended order. Tripping the upstream device first cuts power to every feeder it supplies, not just the faulted one.
    • DIncorrect. With identical settings there is no time margin between devices, so they can't be selective. Coordination needs graded pickup and time-delay settings.
  10. Question 10

    In a feeder protection scheme, how does an overcurrent relay clear a fault?

    • AIt melts an internal element and interrupts the fault current by itself
    • BIt inserts series reactance that holds the fault current at a safe level
    • CIt sends a trip signal to a breaker once current goes above its pickup
    • DIt sends a trip signal to a breaker once power flows into the generator
    Show answer and explanation

    Answer: C) It sends a trip signal to a breaker once current goes above its pickup

    An overcurrent relay compares measured current with its pickup setting. When the current goes above it, usually after a coordinated time delay, the relay signals a circuit breaker to open. The relay never interrupts current itself.

    • AIncorrect. That describes a fuse. A protective relay is a sensing and decision device. It does not interrupt current itself; a circuit breaker does that.
    • BIncorrect. That describes a current-limiting reactor. A reactor lowers the fault current but does not detect the fault or isolate the faulted section.
    • CCorrect. The relay senses current, usually through a current transformer. When the current goes above the pickup setting, often after an inverse-time delay used for coordination, it energizes the breaker trip circuit and the breaker opens.
    • DIncorrect. That describes a reverse-power (directional power) relay, which detects motoring of a generator rather than overcurrent.

Power Systems: FAQs

How much of the FE exam is Power Systems?

Power Systems is 8% of the FE exam by the official exam guide's weighting, which on a 110-question form works out to roughly 9 questions. The real exam's exact split varies by form.

What does the Power Systems domain cover?

Generating, transmitting and using electric power: single- and three-phase systems, transformers, machines and power factor.

How should I study Power Systems for FE?

Practise the wye and delta line and phase conversions until they are automatic, keeping the \(\sqrt{3}\) factor in the right place; many power questions rely on it.

Where can I practise more Power Systems questions?

This page has 10 free Power Systems questions with answers. The ExamWize FE question bank has 48 questions in this domain. Every practice exam result breaks your score down by domain, and Review Mode re-drills the questions you missed.

Get Power Systems exam-ready

The full FE bank has 48 Power Systems questions. Timed practice exams match the real exam's length and domain weights, every result shows your score per domain, and Review Mode re-drills the questions you missed.

Not affiliated with NCEES; questions are original, written from the official exam outline, and never copied from the real exam.