FE · 4% of the exam
Instrumentation and Controls practice questions
10 free Instrumentation and Controls questions for the FE Other Disciplines Exam (FE) exam, each with the correct answer and an explanation for every option.
What this domain covers
The smallest domain: how physical quantities are measured and how feedback systems keep a process at its set point.
- Exam weight
- 4%
- On a real exam
- ≈ 4 questions
- In our bank
- 24 questions
Topics that come up most
- Sensors and transducers such as thermocouples and strain gauges
- Measurement accuracy, precision and uncertainty
- Block diagrams and transfer functions
- Feedback control and controller response
- Data acquisition and signal conditioning
How to study it
Practise reducing block diagrams to a single transfer function; it is a mechanical skill that pays off quickly with a little repetition.
Sample Instrumentation and Controls questions
Try each one before opening the answer. Original questions written to the official exam objectives.
Question 1
An 8-bit analog-to-digital converter spans 0 to 5 V. Its resolution is about:
- A4.9 mV, using 10 bits
- B0.625 V, dividing by 8
- C19.5 mV
- D1.95 mV
Show answer and explanation
Answer: C) 19.5 mV
- AIncorrect. That's 1,024 levels.
- BIncorrect. There are 256 levels.
- CCorrect. An 8-bit converter has 2⁸ = 256 levels, so 5 V ÷ 256.
- DIncorrect. That's off by a factor of 10.
Question 2
In a PID controller, the derivative term mainly responds to:
- AThe rate of change of the error
- BThe accumulated past error
- CThe present error only
- DThe sensor's calibration date
Show answer and explanation
Answer: A) The rate of change of the error
- ACorrect. It adds damping and anticipation.
- BIncorrect. That's the integral term.
- CIncorrect. That's the proportional term.
- DIncorrect. That isn't related.
Question 3
A thermocouple's reference junction is at a terminal block whose temperature drifts during the day. Without compensation, the indicated process temperature will drift. This is because the thermocouple's output voltage is set mainly by:
- AThe absolute temperature of the measuring junction alone
- BThe temperature difference between the two junctions
- CThe total electrical resistance of the lead wires
- DThe excitation current supplied by the readout device
Show answer and explanation
Answer: B) The temperature difference between the two junctions
Thermocouple voltage depends on the temperature difference between the measuring and reference (cold) junctions. Cold-junction compensation measures the reference temperature and corrects for it.
- AIncorrect. A thermocouple does not measure absolute temperature. The same measuring-junction temperature gives a different voltage when the reference temperature changes.
- BCorrect. The Seebeck voltage depends on the temperature difference between the measuring and reference junctions. The reference temperature must be known, or compensated for, to find the process temperature.
- CIncorrect. Lead resistance matters little with a high-impedance voltage measurement, and it does not generate the thermoelectric voltage.
- DIncorrect. A thermocouple generates its own voltage and needs no excitation, unlike an RTD or thermistor.
Question 4
A Bourdon tube is a common sensing element for measuring:
- ATemperature
- BPressure
- CElectrical current
- DLight intensity
Show answer and explanation
Answer: B) Pressure
- AIncorrect. It responds to pressure.
- BCorrect. The curved tube straightens as pressure rises.
- CIncorrect. It responds to pressure.
- DIncorrect. It responds to pressure.
Question 5
In a strain gauge bridge, a "dummy" gauge on an unstrained piece of the same material is used mainly to:
- ADouble the output from strain
- BCompensate for temperature effects
- CMeasure pressure instead of strain
- DReplace the power supply
Show answer and explanation
Answer: B) Compensate for temperature effects
- AIncorrect. Its purpose is compensation.
- BCorrect. Both gauges change equally with temperature.
- CIncorrect. That isn't its role.
- DIncorrect. That isn't its role.
Question 6
A strain gauge shows a relative resistance change of 0.002 at a strain of 0.001. Its gauge factor is:
- A0.5
- B2
- C0.000002
- D20
Show answer and explanation
Answer: B) 2
- AIncorrect. That's inverted.
- BCorrect. GF = (ΔR/R)/ε = 0.002/0.001.
- CIncorrect. Divide, don't multiply.
- DIncorrect. Recheck the division.
Question 7
An ideal 10-bit analog-to-digital converter that rounds to the nearest code has an input range of 0 to 5 V. What is the maximum quantization error?
- A±4.88 mV
- B±2.44 mV
- C±1.22 mV
- D±9.77 mV
Show answer and explanation
Answer: B) ±2.44 mV
Resolution (1 LSB) = full-scale range/2^n = 5/1,024 ≈ 4.88 mV. An ideal rounding ADC has a maximum quantization error of ±½ LSB ≈ ±2.44 mV.
- AIncorrect. 4.88 mV (5 V/1,024) is one full LSB, the size of one step. A rounding converter is never more than half a step off.
- BCorrect. One LSB = 5 V/2^10 ≈ 4.88 mV. Rounding limits the error to ±½ LSB ≈ ±2.44 mV.
- CIncorrect. This is a quarter LSB, which understates the worst-case rounding error by half.
- DIncorrect. This comes from using 2^9 = 512 levels (5 V/512) instead of 2^10 = 1,024. It is not the ±½ LSB bound.
Question 8
A transducer is a device that:
- AStores data permanently
- BConverts one form of energy into another
- CGenerates power for a plant
- DOnly displays readings
Show answer and explanation
Answer: B) Converts one form of energy into another
- AIncorrect. That's memory.
- BCorrect. Sensors often use transducers.
- CIncorrect. That's a generator.
- DIncorrect. That's an indicator.
Question 9
A tank heater uses simple on-off control with a small deadband (differential) around the setpoint. Once the system is running normally, what temperature behavior should you expect?
- ATemperature settles at a fixed value with no oscillation
- BTemperature cycles continuously in a band about the setpoint
- CTemperature holds a steady offset below the setpoint
- DTemperature oscillates with steadily growing amplitude
Show answer and explanation
Answer: B) Temperature cycles continuously in a band about the setpoint
On-off (bang-bang) control switches the heater fully on or off, so the temperature cycles above and below the setpoint. The deadband sets the band and limits how often the heater switches.
- AIncorrect. The output can only be fully on or fully off, so the heat input cannot settle at the exact level needed to hold one temperature.
- BCorrect. The heater switches on below the lower limit and off above the upper limit. This causes a sustained cycle whose size depends on the deadband and the process lag.
- CIncorrect. A steady offset with no cycling is typical of proportional-only control, not on-off control.
- DIncorrect. On-off control produces a bounded, sustained cycle, not an unstable oscillation that keeps growing.
Question 10
In a feedback control system, the error signal is:
- AThe setpoint minus the measured value
- BThe measured value only
- CThe controller output
- DThe disturbance acting on the process
Show answer and explanation
Answer: A) The setpoint minus the measured value
- ACorrect. The controller acts to reduce it.
- BIncorrect. It's the difference from the setpoint.
- CIncorrect. That's the corrective action.
- DIncorrect. That isn't the error signal.
Instrumentation and Controls: FAQs
How much of the FE exam is Instrumentation and Controls?
Instrumentation and Controls is 4% of the FE exam by the official exam guide's weighting, which on a 110-question form works out to roughly 4 questions. The real exam's exact split varies by form.
What does the Instrumentation and Controls domain cover?
The smallest domain: how physical quantities are measured and how feedback systems keep a process at its set point.
How should I study Instrumentation and Controls for FE?
Practise reducing block diagrams to a single transfer function; it is a mechanical skill that pays off quickly with a little repetition.
Where can I practise more Instrumentation and Controls questions?
This page has 10 free Instrumentation and Controls questions with answers. The ExamWize FE question bank has 24 questions in this domain. Every practice exam result breaks your score down by domain, and Review Mode re-drills the questions you missed.
Other FE topics
- Mathematics8% of the exam
- Probability and Statistics6% of the exam
- Chemistry5% of the exam
- Engineering Ethics and Societal Impacts5% of the exam
- Safety, Health, and Environment6% of the exam
- Engineering Economics6% of the exam
- Statics9% of the exam
- Dynamics9% of the exam
- Strength of Materials9% of the exam
- Materials6% of the exam
- Fluid Mechanics12% of the exam
- Basic Electrical Engineering6% of the exam
- Thermodynamics and Heat Transfer9% of the exam
Also: 15 free questions across all topics, the FE cheat sheet and the study guide.
Get Instrumentation and Controls exam-ready
The full FE bank has 24 Instrumentation and Controls questions. Timed practice exams match the real exam's length and domain weights, every result shows your score per domain, and Review Mode re-drills the questions you missed.
Not affiliated with NCEES; questions are original, written from the official exam outline, and never copied from the real exam.